Copper busbars for electrical cabinets: rigid bars vs flexible connections
In any power electrical cabinet, from low-voltage switchgear to the main busbar of a substation, copper is distributed along two different paths. Straight, stable runs carrying current are resolved with a rigid bar. Sections that absorb movement, thermal expansion or vibration are resolved with a flexible connection. And a large share of cabinet maintenance problems appear precisely where someone made the wrong choice between the two.
This article compares both types, explains how the designer picks each one, and describes the hybrid cases where they coexist.
What a busbar is and what it does
A busbar is the system of rigid conductors that distributes electrical current inside a cabinet or enclosure, from the incoming feeder to the outputs of each protected circuit. It has three functions:
- Carry nominal current without exceeding admissible temperature
- Withstand the electrodynamic forces of a short-circuit without deformation
- Maintain insulation distances between phases and to ground
In low-voltage industrial applications, busbars are almost always built from copper bars — sometimes aluminium — bolted to insulating supports. In medium voltage and substations the geometry becomes more complex and tubes, profiles or special busbar systems appear.
Rigid copper bar — characteristics and typical use
A rigid bar is a C1100 copper bar of rectangular cross-section, in hard or semi-hard temper, with standardised dimensions (typically between 12×2 mm and 100×10 mm in industrial cabinets, larger in substations).
Its advantages:
- High current-carrying capacity per unit cost
- Good heat dissipation thanks to its large external surface
- Easy to machine (drilling, gentle bends) and to bolt
- Dimensionally stable, no intermediate supports required in short runs
Its limitations:
- Absolute rigidity: absorbs no movement, expansion or vibration
- Any deformation is transmitted entirely to the joint points, risking bolt loosening
- Laborious installation when cabinet geometry requires multiple bends
- Coplanarity defects between busbar and equipment generate permanent mechanical stress
Typical application: distribution in main cabinets, vertical column busbars, connections between equipment aligned on the same frame.
Flexible copper connection — characteristics and typical use
A flexible connection replaces the rigid bar in a specific section with a construction that absorbs movement. The three common constructions are:
- Flat copper braid: fine strands braided and formed to flat geometry with crimped or cast terminals at each end
- Laminated flexible bar: a pack of thin copper laminations (0.1–0.5 mm thick each) stacked and joined only at the ends, allowing relative sliding between laminations
- Flat connection with terminals: flat braid with integrated terminals, ready to be bolted directly to equipment
Its advantages:
- Absorbs thermal expansion from adjacent rigid conductors
- Absorbs mechanical vibration (transformers, motors, switchgear with frequent operation)
- Compensates misalignment between equipment and busbar without transmitting stress
- Simplifies dismounting and maintenance of individual equipment
- Absorbs slight movements from cabinet or floor settling
Its limitations:
- Higher unit cost than an equivalent rigid bar
- Requires properly executed terminals — a bad crimp is the most common failure
- Takes more volume than a rigid bar of the same electrical cross-section
Direct technical comparison
| Parameter | Rigid bar | Flexible connection |
|---|---|---|
| Thermal expansion absorption | None | High |
| Vibration absorption | None | High |
| Misalignment compensation | No | Yes |
| Cost per meter (same cross-section) | Baseline | 2.5–4× higher |
| Ease of installation in complex geometries | Low | High |
| Heat dissipation | Very good | Good |
| Bolt torque retention | Requires periodic inspection | Better retention |
| Durability under dynamic duty | Poor (joint fatigue) | Good |
Thermal expansion: the main reason to include flexible connections
Copper has a linear thermal expansion coefficient of 17.7 × 10⁻⁶ /°C. A 3-meter rigid bar run that goes from 20 °C ambient to 90 °C service temperature expands by:
ΔL = 3,000 mm × 17.7 × 10⁻⁶ × 70 = 3.72 mm
Nearly 4 millimeters. If that run is rigidly bolted at both ends, those 4 mm have nowhere to go — they become mechanical stress that:
- Loosens bolts through cyclic deformation
- Deforms insulating supports through lateral forces
- Can crack the bars themselves in stress-concentration zones
The standard solution is to insert a flexible connection every 2-3 meters of rigid busbar, or at every point where the busbar connects to equipment whose mass makes it immobile (transformer, power circuit breaker, industrial rectifier). The flexible connection absorbs expansion and mechanically decouples the runs.
Common hybrid cases in industrial cabinets
Transformer-to-main-busbar connection. The transformer secondary is a significant thermal and mechanical mass. Its connection to the low-voltage busbar is always made with flexible connections — usually flat braids with terminals — to decouple thermal expansion and absorb transformer vibration.
Connection to withdrawable circuit breaker. Circuit breakers with withdrawable function require connections that tolerate insertion-withdrawal movement and the mechanical tolerances of the connected position. Resolved with short flexible connections between the breaker’s finger clusters and the fixed busbar.
Bridges between columns of a modular cabinet. When the main busbar crosses from one column to another in a modular cabinet, the small relative movements between columns during transport, mounting and settling are absorbed by flexible connections at the crossing points.
Connection to rectifier or power converter. Power electronics equipment operates at high temperatures and medium-frequency mechanical vibration. Always connected to the busbar with flat braids.
Compensation in long runs. In continuous busbars over 6-8 meters, expansion compensators are inserted at intervals, materialised as short flexible connections.
How to choose the right flexible construction
Once the decision for a flexible section is made, the specific construction depends on geometry and current rating:
- Low to medium current ratings (up to 400 A), standard installation: tinned flat braid with crimped terminals
- High current ratings (400-2,000 A): laminated flexible bar or large-section flat braid with cast terminals
- Very high prospective short-circuit: construction with integral cast terminals such as special connections or the flat pressed-welded connection, avoiding the crimped route because of better heat conduction during the fault
- Aggressive environment (chemical, marine, outdoor railway): always tinned, with additional heat-shrink protection if needed — factory insulated connections are a good option
- EMC requirement: consider a complementary shielding braid over the power connection
For electrical cross-section sizing the same criterion as for any flexible braid applies — admissible current corrected by ambient temperature and grouping, with short-circuit and voltage drop verification. The sizing guide published separately covers the full method.
Common busbar mistakes
- Building the entire busbar with rigid bar to minimise cost. Saves on materials, costs on six-month torque inspections and cyclic failures from fatigue.
- Using a flexible connection where there is no movement. Extra cost with no benefit. A stable, short, aligned run is better resolved with a rigid bar.
- Undersized terminal on the flexible connection. The terminal is the electrically critical point. An undersized terminal creates a thermal bottleneck that degrades the joint over time.
- Failing to allow space for the flexible connection in the cabinet design. Flexible connections take more volume than equivalent rigid bars. If the designer doesn’t account for it, geometries end up forced that cancel the flexibility of the part itself.
- Mixing aluminium and copper without bimetallic transition. Direct connection between aluminium bar and copper terminal produces galvanic corrosion within a few years. Requires specific bimetallic terminals.
Frequently asked questions
What rigid bar cross-section is equivalent to an X mm² flexible connection?
The electrical cross-section is equivalent if the useful copper is the same. A 240 mm² flat braid is electrically equivalent to a 240 mm² rigid copper bar. The difference is geometric: the braid takes more external volume and dissipates slightly differently.
Can an existing rigid bar be replaced with a flexible connection without changing the rest of the cabinet?
Yes, provided the electrical cross-section and insulation distances are respected, and provided the flexible connection’s terminals are compatible with the existing bolting. It is a common intervention in corrective maintenance of cabinets with overheating problems due to joint fatigue.
Does the flexible connection produce more Joule losses than the rigid bar?
No, if correctly sized. Copper resistance is the same. Incremental losses, if any, are in the terminals — and with properly executed terminals they are negligible.
How many flexible connections does a standard electrical cabinet need?
It depends on topology. In a typical industrial low-voltage cabinet, flexible connections are installed as a minimum at the transformer connection, at every withdrawable circuit breaker, and at the crossing points between columns. In more complex cabinets, every point where the busbar connects to individual equipment of significant mass is resolved with a flexible connection.
Can flexible connections be made to measure for special geometries?
Yes. Length, cross-section, terminal type, insulation and finish are fully customisable. It is the standard practice in project cabinets — each connection is manufactured to spec with the exact dimensions of the location, following a controlled step-by-step manufacturing process.
Next step
The rigid bar vs flexible connection decision is not about cost: it is about what is happening mechanically at that specific point of the cabinet. Where there is movement, expansion or vibration, the flexible connection is the only solution that ages well. Where there is a stable, aligned run, the rigid bar is the right choice.
At Masfarné we manufacture flat braids, flat connections with terminals and custom flexible connections for industrial busbars, especially for the electrical power generation and distribution and industrial sectors, to technical specification and with crimped, welded or cast terminals depending on the application.
Need custom flexible connections for a cabinet or busbar? Tell us about your project