How to size a flexible copper braid: cross-section, current rating, temperature and flex cycles
Sizing a flexible copper braid is not about picking the largest cross-section that fits. It is about finding the point where three constraints balance: the current that will flow, the temperature the braid can reach without degrading, and the flex cycles it will withstand in service. Over-sizing costs money and reduces flexibility; under-sizing causes overheating, unexpected voltage drops and premature fatigue.
This guide walks through the sizing method step by step, with the correction factors that apply in real installation scenarios.
The three sizing criteria
Every flexible braid is sized by satisfying three criteria simultaneously. The final cross-section is the largest of the three:
- Thermal criterion: the braid must not exceed its maximum service temperature at nominal current
- Voltage drop criterion: the voltage loss between ends must stay below the admissible limit
- Mechanical criterion: the braid must withstand the expected flex cycles without fatiguing
For short connections (< 1 m), the thermal criterion almost always dominates. For long braids or low-current applications, voltage drop may take over. In dynamic applications — robotic arms, thermal expansion compensation, cabinet doors — the mechanical criterion may demand far more cross-section than current alone would require.
Step 1 — Define nominal current and duty cycle
Before applying any table, you need to define precisely:
- Nominal current (In): RMS value in steady-state operation
- Prospective short-circuit current (Isc): peak value during fault, with its duration
- Duty type: continuous (S1), intermittent (S3), repeated cycle… Intermittent duty allows reduced cross-section compared to continuous
- Diversity factor if multiple braids share current in parallel
A common mistake: sizing by the equipment’s In without considering Isc. A braid correctly sized for nominal current can melt during a short-circuit if its cross-section cannot absorb the fault’s specific energy (I²t).
Step 2 — Thermal sizing calculation
Admissible current in a flexible braid depends on three factors:
- Effective copper cross-section
- Ambient installation temperature
- Heat dissipation conditions (free air, inside cable tray, in contact with heated surface)
As a reference, these are the admissible currents for C1100 copper braids, bare, in free air, at 30 °C ambient temperature and with 90 °C maximum service temperature:
| Cross-section (mm²) | Admissible current (A) — continuous duty |
|---|---|
| 6 | 60 |
| 10 | 85 |
| 16 | 115 |
| 25 | 150 |
| 35 | 185 |
| 50 | 235 |
| 70 | 290 |
| 95 | 350 |
| 120 | 405 |
| 150 | 465 |
| 185 | 530 |
| 240 | 620 |
| 300 | 715 |
These values must be corrected with two factors according to real conditions:
Ambient temperature correction factor:
| Ambient temperature | Factor |
|---|---|
| 20 °C | 1.08 |
| 30 °C | 1.00 |
| 40 °C | 0.91 |
| 50 °C | 0.82 |
| 60 °C | 0.71 |
| 70 °C | 0.58 |
Grouping correction factor (several parallel or bundled braids):
| Number of grouped braids | Factor |
|---|---|
| 2 | 0.85 |
| 3 | 0.79 |
| 4 | 0.75 |
| 6 | 0.70 |
| 9 or more | 0.65 |
Corrected admissible current: Iadm = Itable × Ftemp × Fgrouping
If the corrected Iadm is lower than the circuit’s nominal current, step up to the next cross-section.
Step 3 — Voltage drop calculation
Voltage drop is negligible in short braids, but in runs of several meters — typical in substation busbars or long equipotential interconnections — it can become the dominant criterion.
Voltage drop in DC or low-frequency AC is calculated as:
ΔU = (2 × ρ × L × I) / S
Where ρ is the resistivity of copper (0.0172 Ω·mm²/m at 20 °C — remember it rises with working temperature), L is length in meters, I is current in amps and S is cross-section in mm².
In AC the reactive term must be added, which in flexible braids is normally negligible compared to the resistive term except at high frequency — and for high frequency the right solution is not a braid but a Litz wire.
Step 4 — Flex cycle correction
A moving braid fatigues. Individual strands undergo alternating stresses each time the braid flexes, and from a certain number of cycles they begin to break. The braid construction — individual strand diameter, lay length, braid density — determines its dynamic behavior.
Three duty regimes require different factors:
Static duty: braid installed and practically immobile (normal thermal expansion compensation, fixed equipotential bonding). No correction required. Service life equivalent to the equipment, 20-40 years. This is the typical regime for flat braids and flat connections with terminals in busbars.
Semi-dynamic duty: occasional flexing (cabinet doors, removable components for maintenance). Recommended to increase cross-section by 15-20% over the thermal calculation, or specify an “extra flexible” construction with smaller individual strand diameter.
Dynamic duty: continuous repeated flexing (robotic arms, drag chains, applications with over 10⁴ expected cycles). Here thermal sizing is secondary and construction dominates. Specify extra-flexible braid with 0.10-0.15 mm strands and short lay length, and in many cases choose extra-flexible cables over braids proper. For geometries with multi-axial torsion, spiroid braids are the usual construction.
Step 5 — Short-circuit oversizing
In installations with high Isc — substations, generator outputs, main busbars — verify that the cross-section withstands the I²t of the fault during the protection’s operating time.
Minimum cross-section for short-circuit is calculated as:
Smin = I × √t / k
Where I is the RMS short-circuit current, t is operating time in seconds, and k is a constant depending on material and initial/final admissible temperatures. For bare copper with initial 30 °C and final 250 °C, k ≈ 226.
If the cross-section chosen by thermal criterion does not meet the short-circuit minimum, step up. In applications with very high Isc, cast-end terminals are used — typical construction of special connections and the flat pressed-welded connection — for their better thermal conductivity during the fault.
Practical sizing example
Scenario: equipotential connection in the main busbar of a railway traction substation. Nominal current 400 A, short-circuit 20 kA for 200 ms, ambient temperature 45 °C, 3 grouped braids, static duty, length 1.5 m.
Thermal calculation:
- Required current: 400 A
- Temperature factor (45 °C): ≈ 0.87
- Grouping factor (3 braids): 0.79
- Equivalent current for table lookup: 400 / (0.87 × 0.79) = 582 A
- Table cross-section: 185 mm² (530 A) insufficient → step up to 240 mm² (620 A) ✓
Short-circuit calculation:
- Smin = 20,000 × √0.2 / 226 = 39.6 mm² → met by 240 mm² ✓
Voltage drop:
- ΔU = (2 × 0.0172 × 1.5 × 400) / 240 = 0.086 V — negligible ✓
Final solution: tinned flexible copper braid, 240 mm² cross-section, 1.5 m length, with tinned crimped terminals. Static duty, no need for extra-flexible construction. This is a common configuration in electrical power generation and distribution installations.
Common sizing mistakes
- Sizing by the feeder cable cross-section instead of by actual current. The feeder cable may be oversized for other reasons (long run, differential protection); the braid does not need to replicate that cross-section.
- Ignoring the grouping factor when several braids share a cable tray or junction box. It reduces admissible current by 15% to 35% depending on quantity.
- Confusing nominal with effective cross-section. The nominal cross-section of a braid is the sum of individual strand sections. The effective cross-section for thermal conduction is slightly lower due to the braid lay — for standard braids the difference is between 3% and 8%.
- Forgetting short-circuit. This is the most ignored criterion and the one that produces the most spectacular failures when the fault occurs.
- Choosing bare copper in aggressive environments to save on tinning. Oxidation degrades the electrical joint within months and blows up any previous calculation.
Frequently asked questions
Does the same current table apply to bare and tinned braid?
Yes, copper conductivity does not change with tinning in DC or low-frequency operation. Admissible currents are practically identical.
How long does a braid take to reach stable temperature?
It depends on cross-section and ventilation conditions. As an order of magnitude, small sections (< 25 mm²) stabilize in 15-30 minutes; large sections (> 150 mm²) can take 1-2 hours. A proper thermal test requires at least that waiting period.
Can cross-section be reduced if the braid is cooled by forced ventilation?
Yes, a positive correction factor can be applied if forced convection is demonstrable. In industrial practice it is rarely documented and designers prefer to size for natural convection with margin.
What is the maximum admissible service temperature of a braid?
For bare braid in free air, 90 °C is the standard value. For insulated braid, maximum temperature is set by the insulation (70 °C for standard PVC, 90 °C for high-temp PVC, 105 °C for silicone, 180 °C for special silicones). Exceeding the insulation limit degrades the material and eliminates electrical protection.
Do the same factors as for a conventional electrical cable apply?
General criteria are the same, but current rating tables are not identical. A flexible braid dissipates heat better than an equivalent insulated cable due to its open construction and larger external surface. Using cable tables would slightly underestimate braid capacity.
Next step
Correct sizing of a flexible braid crosses four domains — electrical, thermal, mechanical and installation — and requires specific project data that is not always clear in the initial specification. If you have a technical spec to size, or doubts about which cross-section to specify, Masfarné’s technical team runs the calculation with your input data and proposes the specific construction.